Duwei DW151 differential pressure transmitter is a customized special product for air conditioning units. It adopts the intelligent embedded software algorithm and unique temperature compensation technology developed by Dewey to solve the problems of zero drift of air pressure measurement, frequent pulsation of pressure change and nonlinear output.
1、 Overview
Duwei DW151 differential pressure transmitter is a special product for air conditioning unit. It adopts intelligent embedded software algorithm and unique temperature compensation technology developed by Dewey to solve the problems of zero drift, frequent pressure variation and nonlinear output of air pressure measurement of air conditioning unit.
2、 Product characteristics
Solid aluminum alloy housing
Meet the requirements of clean industry
Led glow display, intuitive reading, clear
Resolution 0.1pA, digital compensation, good stability
High precision: 1% FS (general)
Auto Zero: zero can be calibrated automatically
3、 Technical parameters
Accuracy (F.S): ± 1% FS accuracy includes linearity, hysteresis and repeatability
Stability: < 0.5% FS / year
Response time: 250ms
Temperature range: storage temperature: 40-85 ℃ working temperature: - 15-70 ℃
Temperature drift: ± 0.03% FS / year
Installation location influence: ± 1% / g
Output signal: two lines 4-20mA
Power supply: 24VDC
Wiring protection: reverse wiring protection
Pressure interface: 1/8 "tower joint
Shell: cast aluminum shell, dark grey coating, resistant to 168 hour salt spray test
Measuring medium: clean, dry, non corrosive gas
Maximum overpressure: range fs*10
Protection grade: IP65
4、 Overall dimensions
blob.png
5、 Installation method
Surface installation: drill 3 equal distance holes with the same size and equal distance on the circumference with diameter of Φ 4-1/16 M2 (103mm), and connect them with the 3 holes on the back of the table, and fix them with 6-32 # screws of appropriate length.
Embedded installation: select a flat plate with diameter of Φ 4-31 / 64 M2 (114mm) with opening diameter, insert differential pressure gauge into the flat plate, and fix the meter in proper position with 6 screws provided in the accessory package.
Note: differential pressure transmitter must be installed vertically when using it!
6、 Electrical connection
If no output is required, connect the positive pole of 24V DC constant voltage power supply to the instrument terminal "+" and the negative pole of DC constant voltage power supply to the instrument terminal "-".
The wiring method for the output change is as follows:
blob.png
Note: when wiring, the power supply must be disconnected!
7、 Selection list
blob.png
For example: product code dw151-1-m, which is represented as DW151, range 0-60pa-10kpa, side installation.